Copyright©Chengdu Huayi Heat Shrink Material Co., Ltd.
Heat Shrink Tubing for Busbar
basic information
Heat shrink tubing for busbar is a type of special heat shrink tubing often used for insulating square, round or rectangular bus bar which is rated from 10kV-35kV. It can also be used for inline bolted connections of rectangular bus bars. The tubing is a cross-linked polyolefin and in colors. This tubing has good solvent and excellent tracking resistance as well as high resistance to splitting.The tubing shrinks easily to form the insulating cover.
Part No.
|
Busbar width(mm)
|
Before shrink(mm)
|
After shrink(mm)
|
||
Inside diameter
|
Wall thickness
|
Inside diameter
|
Wall thickness
|
||
10 KV HMPG 20
|
20
|
20±0.8
|
1.0±0.2
|
9
|
2.5±0.2
|
10 KV HMPG 30
|
30
|
30±0.8
|
1.0±0.2
|
13
|
2.5±0.2
|
10 KV HMPG 40
|
40
|
40±1.0
|
1.2±0.2
|
15
|
2.8±0.2
|
10 KV HMPG 50
|
50
|
50±2.0
|
1.2±0.2
|
20
|
2.8±0.2
|
10 KV HMPG 60/65
|
60
|
65±3.0
|
1.2±0.2
|
24
|
2.8±0.2
|
10 KV HMPG 80
|
80
|
80±3.0
|
1.2±0.3
|
32
|
2.8±0.2
|
10 KV HMPG 100
|
100
|
100±4.0
|
1.2±0.3
|
40
|
2.8±0.2
|
10 KV HMPG 120
|
120
|
120±4.0
|
1.2±0.3
|
48
|
2.8±0.2
|
10 KV HMPG 150
|
150
|
150±4.0
|
1.2±0.3
|
60
|
2.8±0.2
|
10 KV HMPG 180
|
180
|
180±5.0
|
1.2±0.3
|
70
|
2.8±0.2
|
10 KV HMPG 210
|
210
|
210±5.0
|
1.2±0.3
|
80
|
2.8±0.2
|
Heat shrink tubing for 35kv busbar
Part No.
|
Busbar width(mm)
|
Before shrink(mm)
|
After shrink(mm)
|
||
Inside diameter
|
Wall thickness
|
Inside diameter
|
Wall thickness
|
||
'35 KV HMPG 30
|
30
|
30±1.0
|
1.9±0.5
|
15
|
4.0±0.3
|
35 KV HMPG 40
|
40
|
40±1.0
|
1.9±0.5
|
20
|
4.0±0.3
|
35 KV HMPG 50
|
50
|
50±2.0
|
1.9±0.5
|
25
|
4.0±0.3
|
35 KV HMPG 60/65
|
60
|
65±2.0
|
1.9±0.5
|
30
|
4.0±0.3
|
35 KV HMPG 80
|
80/100
|
80±3.0
|
1.9±0.5
|
40
|
4.0±0.3
|
35 KV HMPG 100
|
100/120
|
100±4.0
|
1.9±0.5
|
50
|
4.0±0.3
|
35 KV HMPG 120
|
150
|
120±4.0
|
1.9±0.5
|
60
|
4.0±0.3
|
35 KV HMPG 150
|
180
|
150±4.0
|
1.9±0.5
|
75
|
4.0±0.3
|
35 KV HMPG 180
|
MAX
|
180±5.0
|
1.9±0.5
|
90
|
4.0±0.3
|
35 KV HMPG 210
|
MAX
|
210±5.0
|
1.9±0.5
|
105
|
4.0±0.3
|
Busbar protection box
Name
|
Type and Specs
|
Name
|
Type and Specs
|
Name
|
Type and Specs
|
"I" a x b x c
|
"I" a x b x c
|
"L" a x b x c
|
|||
I type
|
I 30 x 30 x 60
|
I type
|
I 30 x 30 x 60
|
I type
|
I 30 x 30 x 60
|
I 40 x 40 x 60
|
I 40 x 40 x 60
|
I 40 x 40 x 60
|
|||
I 50 x 50 x 60
|
I 50 x 50 x 60
|
I 50 x 50 x 60
|
|||
I 60 x 60 x 60
|
I 60 x 60 x 60
|
I 60 x 60 x 60
|
|||
I 80 x 80 x 60
|
I 80 x 80 x 60
|
I 80 x 80 x 60
|
|||
I 100 x 100 x 60
|
I 100 x 100 x 60
|
I 100 x 100 x 60
|
|||
I 120 x 120 x 60
|
I 120 x 120 x 60
|
I 120 x 120 x 60
|
|||
I 150 x 150 x 60
|
I 150 x 150 x 60
|
I 150 x 150 x 60
|
Testing report
User report
keywords:
powe cable accessories heat shrink 10kv 35kv
The next article
Heat Shrink Termination